Electrical Load Calcs
NEC 2023 · Browser-based calculation

Voltage Drop Calculator

Estimate voltage loss along a single-phase, balanced three-phase or two-wire DC circuit. Uses a 75°C pure-resistance model; check ampacity separately.

Based on NEC 2023Runs in your browser
Inputs Local only
1 · Circuit
2 · Conductor & target

Calculation result NEC 2023

Complete the required fields

For estimation only. Results compare loads under the selected NEC method; they do not guarantee permit approval or code compliance. Verify with your local adopted code and a licensed electrician. Disclaimer

How the voltage drop calculator works

Enter actual current, one-way distance, supply voltage and conductor material/size. The model applies the return-path multiplier and a listed 75°C resistance. Compare the unrounded percentage to your target, then try supported sizes from smallest to largest.

Single-phase / two-wire DC: ΔV = 2 × I × R × L / 1,000. Balanced three-phase: ΔV = √3 × I × R × L / 1,000. Drop % = 100 × ΔV / supply voltage.

Worked example

A 120 V single-phase circuit carries 20 A over 100 ft one way on #12 uncoated copper. R = 1.98 Ω/1,000 ft. ΔV = 2 × 20 × 1.98 × 100 / 1,000 = 7.92 V. Drop = 6.60%; receiving voltage = 112.08 V. For a 3% target the first listed size meeting this resistance model is #8 copper: 3.112 V, or 2.59%. Check that size’s ampacity separately.

NEC references

NEC 2023: 210.19; Chapter 9 Table 8. These are reference identifiers, not reproduced code text. Read our methodology and verification limits.

Limitations

No parallel conductors, mixed return paths, plated/solid substitutions, unbalanced three-phase or AC impedance design. The model assumes power factor 1 and zero reactance. 3% branch and 5% combined feeder/branch values are efficiency guidance, not universal pass/fail rules. A loss equal to or greater than the supply is rejected.

For estimation only. Results compare loads under the selected NEC method; they do not guarantee permit approval or code compliance. Verify with your local adopted code and a licensed electrician.

FAQ

Is length one way or round trip?

Enter one-way distance. The model includes the return conductor for single-phase and two-wire DC.

What does the three-phase voltage mean?

Use line-to-line supply voltage for a balanced three-phase circuit.

Does the suggested wire size meet ampacity?

It meets only the selected voltage-drop target under this model. Use the wire-size calculator and check installation requirements.

Why might another tool differ?

A tool that uses power factor, reactance, steel raceway or another temperature can produce a different result. Compare models before comparing numbers.

Does zero current give zero drop?

Yes. It also makes the smallest listed size pass the voltage-drop target, but that does not establish a safe conductor for your circuit.

Related calculators

Planning an EV charger or panel upgrade? Run a load calculation.

Coming soon

Pro is coming soon — join early access

Tell us what would save you time on the next job.

Planned price
$19/month
Planned to include saved projects, branded reports and customer proposals. Panel schedules and photo entry are under consideration. Price and features aren't final.
Most wanted features (optional, choose up to 2)

Only for Pro launch notices and early-access invitations. No automatic email is sent. Data is retained until 12 months after the Pro launch notice, or deleted earlier on request. For deletion: support@electricalloadcalcs.com Requests are handled within 30 days. Privacy details.